Monobloc Outdoor Unit Service Manual
78
4) The alarm count when the compressor stopped with 2) is cleared after the operation continued for 10 minutes. If the alarm
count becomes [10] without clearing, the alarm is determined and reactivation is not performed.
5) For the alarm display [72] contents, confirm check code list.
Discharge Temperature Release Control
1) This function controls the operation frequency, that is, lowers the operation frequency when the discharge temperature has
rapidly risen during PMV control. It subdivides the frequency control up to a unit of 0.6Hz to stabilize the cycle.
2) When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts after 2
minutes 30 seconds. The alarm counter is cleared when it has continued the operation for 10 minutes.
If the abnormal stop zone has been detected by 4 times without clearing the counter, an alarm “74” is displayed.
Heating TR
CP1701H
CP1701H
CP2101H
CP2101H
a
62 °C
62 °C
62 °C
62 °C
b
59 °C
59 °C
59 °C
59 °C
c
57 °C
57 °C
57 °C
57 °C
d
55 °C
55 °C
55 °C
55 °C
e
53 °C
53 °C
53 °C
53 °C
Cooling TL
CP1701H
CP1701H
CP2101H
CP2101H
a
63 °C
63 °C
63 °C
63 °C
b
62 °C
62 °C
62 °C
62 °C
c
60 °C
60 °C
60 °C
60 °C
d
57 °C
57 °C
57 °C
57 °C
e
55 °C
55 °C
55 °C
55 °C
a
b
c
d
e
CP1701H
111
106
100
95
90
CP2101H
115
113
105
102
95
Heating TR / Cooling TL
Abnormal stop
Frequency normal down
Frequency slow down
Frequency hold
Frequency slow up (Up to command)
As command is
a
b
c
d
e
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...