Monobloc Outdoor Unit Service Manual
83
9.4.1.8.
Alarm 21 – Loss of communication with inverter
Electrical connection
Alarm 21
Loss of communication with inverter
NHC board: J26.5
On terminal block of inverter box
(marker 3)
9.4.1.9.
Alarm 22 – Communication failure between inverter boards
Alarm 22
Communication failure between inverter boards
9.4.1.10. Alarms 23 & 24 – Loss of communication with Header / Follower
Alarm 23
Loss of communication with Followers
Electrical connection
Alarm 24
Loss of communication with Header
Bus connection
J6 on NHC board, or terminal block X2: 1; 2; 3
Is the connection NHC board
and inverter box correct?
Correct wiring
NHC or inverter box replacement
NO
YES
Are the connections between the
boards of the inverter box
correct?
Correct wiring
Correct wiring
NO
YES
YES
With user interface, pass from
Header status to Follower status.
If the procedure works, then the bus
connection operate correctly
Does Bus connection operate
correctly?
Check configuration of Header /
Follower installation
Check Bus connection
NO
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...