Monobloc Outdoor Unit Service Manual
58
8.3.2. CAPACITY OVERRIDE [P064]
#
Override
Conditions
Action
0
No override
N.A.
No action
1
Power Up Delay
Unit is powered on
Wait for 90 seconds before starting the
compressor
2
Minimum on time
(compressor short cycle
protection)
Compressor is running for less than 3
minutes.
Do not allow compressor stopping, run
at minimum frequency
3
Minimum off time
(compressor short cycle
protection)
Compressor is stopped for less than 2
minutes and 30 seconds
Do not allow compressor starting
4
Mode Change Delay
Operating Mode is changed
Wait for 30 seconds before starting the
compressor
5
Starting Sequence Step 1
Compressor is starting
Limit maximum Compressor
frequency
6
Starting Sequence Step 2
Compressor is starting
Limit maximum Compressor
frequency
7
Starting Sequence Step 3
Compressor is starting
Limit maximum Compressor
frequency
8
Starting Sequence Step 4
Compressor is starting
Limit maximum Compressor
frequency
9
Compressor Stopping
Delay
Compressor is requested to stop and
current capacity is greater than 1%
Run the compressor at minimum
frequency for 30 seconds
10
No override
N.A.
No action
20
Defrost
Unit is defrosting
No action, monitoring only
39
Minimum OAT in Heating
Heat Mode and TO2 [P039] is below
“oat_min” parameter ([P514], default is
-20°C)
Do not allow the start or stop unit if
already running
40
Maximum OAT in Heating
Heat Mode requested and TO2 is
above “oat_max” parameter ([P515],
default is 30°C, max limit is 99°C).
Do not allow the start or stop unit if
already running.
41
Maximum EWT in Heating
Unit running and EWT is above 59°C
(17kW) or 56°C (21 kW) or unit
stopped and EWT is above 52°C
(17kW) or 49°C (21kW).
Do not allow the start or stop the
compressor if already running
42
Low OAT in Heating
Units 17 and 21 kW running in Heat
Mode and TO2 [P039] ≤-10°C.
Reduce maximum compressor
frequency to 70 Hz (17 and 21 kW)
43
Very Low OAT in Heating
Units 17 and 21 kW running in Heat
Mode and TO2 [P039] ≤ -15°C.
Reduce maximum compressor
frequency to 60 Hz (17 and 21 kW)
44
High OAT in Heating
Units 17 and 21 kW, Heat Mode
requested and TO2 > 30°C.
Do not allow the compressor start or
stop it if already running.
45
High LWT Threshold #1 in
Heating
Units 17 and 21 kW, Heat Mode, TO2
[P039] above 11°C and LWT above
High Temperature Protection threshold
#1 (42°C).
Reduce compressor frequency
range between 45 and 90 Hz
46
High LWT Threshold #2 in
Heating
Units 17 and 21 kW, Heat Mode, TO2
[P039] above 11°C and LWT above
High Temperature Protection threshold
#2 (53°C).
Reduce compressor frequency
range between 45 and 70 Hz
47
High LWT Threshold #3 in
Heating
Units 17 and 21 kW, Heat Mode, TO2
[P039] above 11°C and LWT above
High Temperature Protection threshold
#3 (55°C).
Reduce compressor frequency
range between 30 and 50 Hz
48
High LWT Threshold #4 in
Heating
Units 17 and 21 kW, Heat Mode and
LWT above High Temperature
Protection threshold #4 (55°C).
Reduce maximum compressor
frequency to 80 Hz.
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...