Monobloc Outdoor Unit Service Manual
71
4
“ON” on the remote controller will not operate the compressor.
(It will not operate even after the reboot delay timer elapsed)
When the outdoor temperature (TO sensor detection
temperature) is -25 °C or lower, the heat pump will not operate
in order to protect the compressor, and the heater will operate
instead.
5
When the power is turned on, it starts operation without
operating the remote controller.
• The auto restart operation may be working.
• The antifreeze operation may be working.
• If the TWI, TWO or THO sensor detects a temperature
below 4 °C, the operation changes from circulating pump
--->> circulating pump + heater.)
9.3.
Outline of the determination diagram
The first determination of whether a defective part is in the Monobloc outdoor unit can be performed by the following
method.
9.3.1.
Procedure of defect diagnosis
In the case of a defect, please apply the following procedure in order to find the defective part.
9.3.2.
How to determine the Alarm on the remote controller
Alarms are used to inform you of the failure of one of the parts of the heat pump or chiller system.
In the case of an alarm, the alarm icon is displayed on the RC:
Steady icon: Alarm condition detected; the unit has stopped
Flashing icon: Alarm condition detected; the unit is running
To see the alarms
1.
Press and hold the Mode key and the Schedule key
simultaneously for 2 seconds.
2.
The alarms menu will be displayed.
3.
Press the Down key or the Up key to display the alarms (1 to 5).
Two types of alarms are displayed: Current alarms (C-X) / Past alarms
(P-X).
Examples:
Current Alarm
C1
Past Alarm
P1
Alarm Code
16
Alarm Code
15
Defect
Confirm the check
code on the remote
controller display
Check code
???
Check information and
cause / result
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...