Monobloc Outdoor Unit Service Manual
65
8.4.5. Superheat Control
The superheat is measured with SH=TS - T(Ps) (TS: suction temperature with temperature sensor and
T(Ps): suction saturation temperature calculated from pressure sensor) and it is controlled by PMV opening.
8.4.5.1. Superheat of 17kW unit
Superheat target on 17kW (SH
target
= SH
0 + α)
Compressor frequency
SH0
f< 15
15< f< 38.4
38.4< f< 61.8
61.8< f< 85.2
85.2< f
Cooling mode
6
6
6
6
6
Heating mode
4
4
4
4
4
8.4.5.2. Superheat of 21kW unit
Superheat target on 21kW (SH
target
= SH
0 + α)
Compressor frequency
SH0
f< 42
42< f< 60
60< f< 78
78< f< 96
96< f
Cooling mode
6
6
6
6
6
Heating mode
4
4
4
4
4
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...