154
2
Remote controller
1.How to remove
1) Perform the step 1-1.
2) Remove the remote controller from the holder using
a flat-blade screwdriver. (Release the stopper.)
3) Disconnect the remote controller cable from the
terminal block on the back side of the remote
controller.
2.How to attach
1) Attach it in the reverse order of the removal.
3
Water heat
exchanger board
MCC-1511
1. How to remove
1) Perform the step 1-1.
2) Disconnect the connectors and lead cables
connected to other parts from the water heat
exchanger board.
1. Connector
CN100: TB 01 3P Connector (5P: White)
CN101: Trans (3P: White)
CN102: Trans (6P: White)
CN200: Flow switch (3P: Red)
CN201: Pressure switch (2P: White)
CN202: Bimetal thermostat (3P: Yellow)
CN203: TC sensor (2P: Yellow)
CN204: TWI sensor (3P: Brown)
CN205: TWO sensor (2P: Red)
CN206: THO sensor (3P: White)
CN207: Low pressure sensor (2P: Blue)
CN212: Low pressure sensor (4P: White)
CN213: TB 06 4P Terminal block (3P: White)
CN214: TB 06 4P Terminal block (2P: White)
CN305: TB 01 3P Terminal block (3P: Green)
CN501: Relay board (6P: Yellow)
CN601: Relay 05 (3P: Red)
CN602: TB 04 6P Terminal block (7P: White)
CN603: Pump (3P: Yellow)
CN604: Relay 06, TB 04 4P Terminal block (7P:
Blue)
CN605: Relay 01, Relay 02 (3P: Yellow)
CN606: Relay 03, Relay 04 (3P: Blue)
2. Round-shape terminal
100: Ground (ST2T Ø4 × 8 1 wire)
NOTE
When removing the connector, release the safety lock of
the housing.
3) Release the 6 stoppers of the water heat exchanger
board to remove the board.
No.
Exchange parts name
Work procedure
Remarks
Remote
controller holder
Remote
controller
Remote controller cable
Water heat
exchanger board
Summary of Contents for ESTIA HWS-1501CSHM3-E
Page 196: ...195 220 223 235 234 222 225 226 231 232 229 228 235 233 230 221 224 227 ...
Page 210: ...209 ...
Page 211: ...210 ...
Page 212: ......