[L09] Error
[L16] Error
In DP_SW12-2, 3 of main unit water heat exchanger, if ZONE1 is not set and ZONE2 is set, [L16] displays
abnormality.
Set correctly DP_SW12-2, 3.
No
Set indoor unit capacity data
Setting item code (FC_01)
8 kW = 12
14 kW = 17
Water heat exchange control
board (MCC-1511) Check
If defective, replace it
Yes
Hydro unit capacity
is not set