Hydro unit and Outdoor Unit Settings
Hydro unit
1. Hydro unit Setting
1-1. Setting switch names and positions
1-2. SW02 (System switching 1)
1-3. SW10 (Pump switching)
1-4. SW11 (Heater Yes/No switching)
1-5. SW12 (System switching 2)
SW02
Switching details
Factory default
Remarks
02_1
Boiler install position After 3WV heating side/Before 3WV
After 3WV,
heating
OFF
Before 3 WV
02_2
–
–
OFF
02_3
–
–
OFF
02_4
Room thermostat
No
OFF
SW10
Switching details
Factory default
Remarks
10_1
Pump P1 operation during hot water mode
OFF = P1 ON during heat pump activate
ON = P1 Continues run
Heat-pump
activate
OFF
10_2
Pump P1 operation during room heating. P1 pump stop or
not using out side air temperature.
OFF = Continues run
ON = Pump P1 stop when TO>20
o
C (Available to change
the temperature setting by FC 9E)
Continuous run
OFF
10_3
Pump P2 interlock with P1 Yes/No
Yes
OFF
10_4
–
–
OFF
SW11
Switching details
Factory default
Remarks
11_1
Hydro unit backup heater Energized Yes/No
Energised
OFF
11_2
Hot water cylinder heater Energized Yes/No
Energised
OFF
11_3
External booster heater output Enabled Yes/No
Enabled
OFF
11_4
–
–
OFF
SW12
Switching details
Factory default
Remarks
12_1
Hot water supply
Yes
OFF
12_2
ZONE1
Yes
OFF
12_3
ZONE2
No
OFF
12_4
–
–
OFF
SW10
SW01
SW02
SW11
SW12
SW06
SW13
SW07