122
9-4-3. Temperature sensor, temperature-resistance characteristic
table
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors
TD, TL sensors
Typical value
Typical value
Temperature
(°C)
Resistance value (k
Ω
)
Temperature
(°C)
Resistance value (k
Ω
)
(Minimum)
(Standard)
(Maximum)
(Minimum)
(Standard)
(Maximum)
-10
55.42
55.73
60.04
0
150.5
161.3
172.7
0
32.33
33.80
35.30
10
92.76
99.05
105.6
10
19.63
20.35
21.09
20
58.61
62.36
66.26
20
12.23
12.59
12.95
25
47.01
49.93
52.97
25
9.75
10.00
10.25
30
37.93
40.22
42.59
30
7.764
7.990
8.218
40
25.12
26.55
28.03
40
5.013
5.192
5.375
50
17.00
17.92
18.86
50
3.312
3.451
3.594
60
11.74
12.34
12.95
60
2.236
2.343
2.454
70
8.269
8.668
9.074
70
1.540
1.623
1.709
80
5.925
6.195
6.470
80
1.082
1.146
1.213
90
4.321
4.507
4.696
90
0.7740
0.8237
0.8761
100
3.205
3.336
3.468
100
0.5634
0.6023
0.6434
0
-10
0
10
20
30
40
50
60
10
20
30
40
50
60
70
80
90
100
0
0
0
5
10
15
20
50
100
150
200
10
20
30
40
50
60
70
80
90
100
Resistance(k
Ω)
Temperature(°C)
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors
Resistance(k
Ω
)(50
°C
or lower)
Resistance(k
Ω
)(50
°C
or higher)
Temperature(°C)
TD, TL sensors
* Since the TH sensor (outdoor unit heat-sink temperature sensor) is built in the
outdoor control board, the resistance value cannot be measured.
Summary of Contents for ESTIA HWS-1501CSHM3-E
Page 196: ...195 220 223 235 234 222 225 226 231 232 229 228 235 233 230 221 224 227 ...
Page 210: ...209 ...
Page 211: ...210 ...
Page 212: ......