57
8-2.
Operation Mode
and Control
Method
12) AUTO operation
An auto operation sets the water temperature TSC_F depending on the outside air temperature TO by following the table below.
1) How to operate
• Pressing the remote controller [ZONE1, 2] button and then the [AUTO] button starts AUTO operation for heating. An
operation starts at the set temperature of straight -line approximation for the following: water temperature 40°C with
the outside temperature -20°C (FC), 35°C with -10 °C (T1)(FC), 30°C with 0°C (FC), 25°C with 10°C (T3), and 20°C
with 20°C (TC).
• For 2-temperature control, although Auto-Curve in ZONE2 shows 80% of that of ZONE1 (FC), the water temperature
setting does not fall below 20°C.
• During an AUTO operation, pressing again the [AUTO] button returns to the usual manual set heating operation.
• The remote controller displays "A" as the temperature during an AUTO operation.
(When 2-temperature control is enabled, the remote controller displays "A".)
• Long-pressing the [AUTO] button during an AUTO operation activates the Auto-Curve FC change mode, enabling
the set Auto-Curve water temperature to be shifted by ±5K range (FC_27). When using the auto curve shift function
please note the maximum and minimum water temperature at 55°C and 20°C respectively.
• Even if the temperature setting is changed during an AUTO operation, the operation continues.
• An AUTO operation works with a heating operation only, not with a cooling or a hot water supply operation.
Related FC
13) Night time low-noise operation
A night time low-noise operation reduces operation frequency and the number of outdoor fan rotations for a certain period
during night time as noise control for urban operation.
Maximum operation frequency 40.2 Hz (Hot water supply/ Heating/ Cooling)
Maximum fan tap
460 rpm (803H-E)
500 rpm (1103H-E, 1403H-E)
(1103H8(R)-E, 1403H8(R)-E, 1603H8(R)-E)
The night time low-noise operation is enabled/ disabled by changing the remote controller FC_09.
<How to set> - Refer to “11. Night time Low-noise Setting” on page 139.
1) Press the TEMP.
and TEST
button at the same time for 4 seconds or longer. (Shifted to the night time low-
noise setting mode)
The Code No. field displays "09", and the DATA "0000",
, and
being displayed blink.
2) Press TIME
to set enable "1" or disable "0".
Pressing SET
change DATA and
display to be lit and the setting is confirmed.
(When "1" as enable is set, the night time low-noise setting is enabled, the control starts at the set start time.)
3) Press TEST
to exit the night time low-noise time setting mode. The
and
goes out, returning to its
original status.
Item
Operation flow and applicable data, etc.
-10
(T1)
-20
20(E)
25(D)
30(C)
35(B)
40(A)
0
10
(T3)
20
Auto-Curve
ZONE1
Auto-Curve
ZONE2
FC No.
Setting item
Default
Setting available range
18
Upper limit of cooling set temperature
25°C
20-30°C
19
Lower limit of cooling set temperature
10°C
10-20°C
1A
Upper limit of heating (ZONE1) set temperature
55°C
37-55°C
1B
Lower limit of heating (ZONE1) set temperature
20°C
20-37°C
1C
Upper limit of heating (ZONE2) set temperature
55°C
37-55°C
1D
Lower limit of heating (ZONE2) set temperature
20°C
20-37°C
27
Set temperature shift with heating set to Auto
0
-5 to 5 k
29
Outside air temperature T1 temperature
-10°C
-15-0°C
2B
Outside air temperature T3 temperature
10°C
0-15°C
2C
Set temperature when out side air temperature is -20 °C.
40°C
20-55°C
2D
Set temperature when out side air temperature is -10 °C (T1).
35°C
20-55°C
2E
Set temperature when out side air temperature is 0 °C.
30°C
20-55°C
2F
Set temperature when out side air temperature is 10 °C (T3).
25°C
20-55°C
30
Set temperature when out side air temperature is 20 °C.
20°C
20-55°C
31
Auto-Curve ratio of ZONE2
80%
0-100%
Summary of Contents for ESTIA HWS-1501CSHM3-E