112
[L29]
<Indication 1> <Indication 2>
[Gas leakage failure]
→
See [P15] details
<Indication 1> <Indication 2>
[4-way valve invert failure]
→
See [P19] details
[P03]
<Indication 1> <Indication 2>
[Abnormal outlet temperature]
Check code
Outdoor LED
indication
Check and Action procedure
(No specific description indicates outdoor unit parts.)
No gas leakage.
Appropriate refrigerant amount.
Correct defective portion
Re-charge refrigerant
Check outdoor control board
If defective, replace it
No
Yes
Pulse motor valve is normal.
Correct defective portion
Replace defective parts
No
Yes
Abnormally over loaded
Deal with or remove
causes
Yes
No
CN603 connector is normal.
TD sensor resistance is normal
Correct connector
Replace sensor
No
Yes
PC-Board
803H-E(MCC-1571)
1103 to 1403H-E (MCC-1571)
1103 to 1603H8(R)-E (MCC 1596)