104
[F14] Error TTW sensor failure
[F17] Error TFI sensor failure
[F18] Error THO sensor failure
Correct TTW sensor
connection
Replace TTW sensor
No
No
TTW sensor
connector (CN214) is
connected
Yes
TTW sensor
characteristic is normal
Yes
Start
Replace water heat exchange control board
(Refer to Charasteristic table on page 122)
Correct TFI sensor
connection
Replace TFI sensor
No
No
TFI sensor
connector (CN213) is
connected
Yes
TFI sensor
characteristic is normal
Yes
Start
Replace water heat exchange control board
(Refer to Charasteristic table on page 122)
Correct THO sensor
connection
Replace THO sensor
No
No
THO sensor
connector (CN206) is
connected
Yes
THO sensor
characteristic is normal
Yes
Start
Replace water heat exchange control board
(Refer to Charasteristic table on page 122)