131
Remote controller function code table
2-3. How to reset hydro function code
If the hydro unit PCB has been replaced, it is necessary to change the FC 01 (capacity setting)
(1) Preparation
1) Turn all of the remote controls "OFF" for the hot water supply [HOTWATER] and heating [ZONE1,2].
2) Turn off the power supply of the hydro unit and the outdoor unit.
3) Remove the front panel of the hydro unit and cover to the hydro unit electrical box.
4) Set SW06_1 and _2 "ON".
(2) Procedure
1) Turn on the power supply of the hydro unit and the outdoor unit.
•
The small yellow LED located near the MCU should be flashing slowly.
2) Press tactile switch SW07 until the yellow LED turns off.
•
When the tactile switch SW07 has been press for 5 sec, flashing becomes quickly. And when the
switch will be pressed further 5 sec, the yellow LED will turn off.
When the SW07 is released, the yellow LED start to flash quickly again.
3) Turn off the power supply of the hydro unit and the outdoor unit.
4) Set SW06_1 and _2 to "OFF".
5) Replace the electrical box cover and front panel on the hydro unit.
2-4. How to reset remote controller function code
It is not possible to reset the remote controller function code setting back to the default values.
FC
Item
Details
Fist shipment
02
Temperature correction by the room temperature sensor
(heating)
-10K~+10K: By 1K steps
-1: -1K correction
03
Temperature correction by the room temperature sensor
(cooling)
-10K~+10K: By 1K steps
-1: -1K correction
05
24H/12H display switching
0: 24H display
1: 12H (AM/PM) display
0: 24H display
09
Night time low-noise mode
0: Invalid
1: Valid
0: Invalid
0A
Night time low-noise start time
0 - 23 (0:00 to 23:00)
22: 22:00
0B
Night time low-noise end time
0 - 23 (0:00 to 23:00)
06: 06:00
0C
Anti bacteria start time
0 - 23 (0:00 to 23:00)
22: 22:00
0D
Anti bacteria start cycle
1 - 10 (Every day to 10-day cycle)
07: 7-day cycle
0E
Starting time of Night set back
0 - 23 (0:00 to 23:00)
22: 22:00
0F
Ending time of Night set back
0 - 23 (0:00 to 23:00)
06: 06:00
11
Remote control Alarm Tone.
0: Alarm Tone OFF
1: Alarm Tone ON
1: Alarm Tone ON
12
Frost running period (days)
(0 days – 20 days)
00: No setting
13
Frost running period (hours)
(0 hours – 23 hours)
00: No setting
SW06