175
4
Electric parts
replacement
2. Reactor
1) Perform the step 1-1.
2) Remove the reactor lead connected to the control
board.
CN05 White, CN06 White
3) Cut the binding tie that binds the compressor leads
and fan motor leads.
4) Remove the reactor.
(Truss B tight screw Ø4 × 6, 2 screw)
5) Attach a new reactor.
NOTE
Be sure to bind the removed binding tie by using the
commercially available binding tie.
Make sure that the fan motor lead and the reactor body
do not contact each other.
No.
Exchange parts
name
Work procedure
Remarks
Reactor lead
Reactor lead
Reactor body
Fan motor lead
Binding tie
(Compressor lead,
Reactor lead)
Binding tie
(Compressor lead,
Reactor lead)
Binding tie
(Fan motor lead,
Reactor lead)
Control board