130
52
External input contact logic (must be used in with
FC61)
0000: CLOSE to stop system *2
0001: OPEN to stop system *2
0002: OPEN to stop system, CLOSE to restart
system (Statics input)
0003: CLOSE to stop system, CLOSE again to restart
system (plus input)
0000:CLOSE to stop
54
Logic of 3-way valve’s action when powered (Single
return only)
0000: Not reversed (Hot water mode when powered)
0001: Reversed (Heating when powered)
0000: Not reversed
(Hot water mode when
powered)
58
Night set back is activated
0000: Zone 1 & 2
0001: Zone 1 only
0000: Zone1 & 2
59
Interval of Mixing Valve control
0001: 1 minute
-
0030: 30 minutes
0004: 4 minutes
5A
P1 setting while in hot water supply mode
0000: While running HP only
0001: P1 continues running
5B
Boiler running setting
0000: Boiler and HP
0001: Boiler only
0002: Heater
0000: Boiler and HP
61
Changing the target of stopping/starting by external
signal or changing the TEMPO setting
0000: Hot water supply and heating
0001: Keeping initial status *3
0002: Hot water supply only
0003: Heating only
0004: TEMPO1 (Not activate the heaters)
0005: TEMPO2 (Not activate the heaters, inlet pump,
heat pump)
0000: Hot water
supply and heating
62
Activate/deactivate A02 error detection
0000: Activate
0001: Deactivate
0000: Activate
64
Continuously run or stop the P2 pump while cooling
0000: Continuously run P2
0001: Stop P2
0000: Continuous
running
65
P1 pump setting when the thermostat is deactivated in
the room temperature remote control and room
temperature thermostat settings
0000: Continuously run P1
0001: Stop P1 when the thermostat is OFF
0000: Continuous
running
67
Changing the condition of optional output (For the
optional P.C. board connected to CN209)
0000: 1-3 During defrosting
2-3 While compressor is running.
0001: 1-3 As error is detected
2-3 During operation
0000: 1-3 During
defrosting
2-3 While compressor
is running.
92
Upper room temperature limit when cooling
0000: 15°C
-
0055: 30°C
0029: 29°C
93
Lower room temperature limit when cooling
0000: 15°C
-
0055: 30°C
0018: 18°C
94
Upper room temperature limit when heating
0000: 15°C
-
0055: 30°C
0029: 29°C
95
Lower room temperature limit when heating
0000: 15°C
-
0055: 30°C
0018: 18°C
96
Initial water temperature setting when controlling
cooling by the room temperature remote control and
room temperature thermostat
0010: 10°C
-
0055: 25°C
0020: 20°C
9D
Initial water temperature setting when controlling
heating by the room temperature remote control and
room temperature thermostat
0010: 20°C
-
0055: 55°C
0020: 40°C
9E
TO temperature setting to stop the P1 pump during the
middle period heating
0010: 10°C
-
0030: 30°C
0020: 20°C
FC
Item
Details
First shipment
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.