170
(input side)
current
Great outdoor
temperature fluctuations
◎
◎
○
108
High voltage protection of
DC bus line
◎
○
○
Voltage of bus line exceeds
protection values
106
Voltage of DC bus line is
too low
●
○
○
Voltage of bus line falls below
protection values
107
Communication faults
◎
◎
●
Communication between
drive and master control
board
109
Out of step
○
○
○
Compressor falls out of step
113
Circuit fault by current
detection
○
○
●
Abnormal operational
amplifier output voltage
114
Compressor start failure
○
○
◎
Compressor start failure
119
Fault of ambient
temperature sensors on
drive board
○
●
○
Short circuit of ambient
temperature sensors on drive
board
121
Compressor phase loss
○
◎
○
One or two phases of
compressor (U/V/W) are
missed
122
Note: In trouble free status, the green indicator flashes once everytime it receives signal
○
On
◎
Flashing
●
Off
Appendix III Fault Code List of Bantek Fan Drive
Type
Monitor
code
LED
flashing
times
Description
Analysis of causes
Operating
status
00H
Keep
flashing
Module operates
normally
01H
Keep
flashing
Overvoltage stall
1. Voltage input is too high
(> 271 V)
02H
Keep
flashing
Overcurrent stall
1. Fan is overloaded
05H
Keep
flashing
Frequency decrease
due to overcurrent
1. Fan is overloaded
07H
Keep
flashing
Frequency decrease
due to overheat
1. Module dissipates heat
poorly;
2. Ambient temperature is
too high;
Fault
1EH
1
Current fault
1. Module fault
23H
2
Temperature sensor
1. Temperature sensor
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...