115
Fault code
Notes
Not operating
Over-current protection for constant speed
operation
Over-current protection for frequency reducing
Over-current protection for frequency increasing
Over-current protection when power off
Overload protection
Over voltage protection
EEPROM module fault
Low voltage protection
CT fault
CPU fault
Grounding failure protection
Over voltage input protection
Power supply module temperature fault (fan
stops)
Power supply module temperature fault
Main circuit fault
Operating fault
Thermistor fault
Communication fault (RS485)
Hitachi drive fault diagnosis (E007/E031)
1. Connect to monitor software
2. Observe the following error codes of C1/C2 marked by circles
3. Make diagnosis based on error codes of FAN and left diagram
Name
Master unit
Slave unit 1
C1 speed:
C2 speed:
C1 temperature:
C1 error code:
C2 temperature:
C2 error code:
FAN1 current:
FAN1 error code:
FAN2 current:
FAN2 error code:
FAN1 set speed:
FAN2 set speed:
HC1:
HC2:
Total running duration of C1:
Total running duration of C2:
Hitachi compressor drive overload troubleshooting (Voltage of bus line)
Measure voltage of bus line and connect a
multimeter to the line with positive electrode to
P and negative electrode to N
When power supply is connected, voltage
between P and N should be 540V (±20V)
If voltage of bus line is too high or too low,
check rectifying circuit of an upper level
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...