116
Hitachi compressor drive overload troubleshooting (Rectifying circuit)
Observe whether bridge rectifier looks dim or
black. If yes, it can be initially considered bridge
rectifier is burnt
P\N\L1B\L2B\L3B characters cover their
corresponding welding points
If visual observation fails, use a multimeter
(diode gear) to test it after power off Use a
multimeter according to the left diagram
Negative
Negative
Negative
Negative
Negative
Negative
Positive
Positive
Positive
Positive
Positive
Positive