132
2.14 Ambient temperature too high/low
Code displayed:
ODU main board displays E037 (applicable to AA/AS/AX models).
Fault detection method:
Ambient temperature too high/low
Fault identification conditions: ODU starts fault protection and fails to work
properly
Possible causes:
①
Abnormal temperature sensor
②
Abnormal main board
③
External heat sources around ambient temperature sensor
④
Actual ambient temperature too high/low
Troubleshooting:
E037: Ambient temperature
too high/low
Check whether ambient
temperature sensor (TH01) is
normal
Replace ambient
temperature sensor
Ambient temperature is too
high/low
No
Yes
Explain to customer
that it is a kind of
protection
mechanism
No
Restart the unit
Check whether there
are heat sources around the
unit (especially around ambient
temperature sensor)
Remove heat
sources or install the
unit at another place
Yes
No
Whether main board is normal
(abnormal signal transmission)
Replace main board
Yes
No
Yes
2.15 System failure
Code displayed:
ODU main board displays E039 (applicable to AA/AS/AX models).
Fault detection method: ODU nixie tubes display corresponding fault codes
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...