17
1.7 Key ODU Components
①
Compressor
Air inlet
Air jetting port
Air outlet
The
inverter
compressor adopts the low-
temperature and strong heating scroll compressor
that is equipped with the advanced permanent
magnet synchronous motor. Speed: 20-100RPS;
generally, compressor coil has a resistance value
of
2~4
Ω
and insulation resistance
≥
1 M
Ω
.
Features of scroll compressor:
1. Highest efficiency
2. Small rotation torque changes, stable
performance with less vibration and low noises
3. Least components used, simple structure,
compact, low weight and high reliability
4. High requirements for machining precision and
high costs
Model
Compressor
Item No.
TIMS080-100AS/X E655DHD-65D2YG
B7020226
TIMS120AS/X
E705DHD-72D2YG
B7020796
TIMS140-160AS/X E856DHD-80D2YG
B7020743
TITIMS180-240AS
TIMS180-220AX
E655DHD-65D2YG*2
B7020226
TIMS260AS
E705DHD-72D2YG*2
B7020796
TIMS280-320AS
E856DHD-80D2YG*2
B7020743
TIMS080-120AST DS4GK5052FVS
B7020977
TIMS140-180AST AMB78FZDMT
B7021045
②
Electronic expansion valve
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...