41
automatically after 10 minutes; if the failure occurs 3 times in 2 hours, it indicates that the
INV compressor is faulty. The unit needs to be turned on and reset after temporary power
disconnection;
b When failure occurs to two INV compressors at the same time, the unit will
automatically turn off to prevent damages. After the power is resumed, reset the unit.
3.4 Current protection of inverter compressor
The unit’s compressor drive module detects the compressor operating current and hence
to provide feedback. See details below
E655DHD:
When I(INV)
≥
22A for 4s, the corresponding INV compressor sends compressor current
overload protection alarms (remove error data after 5 minutes) and the unit recovers after
10 minutes; if compressor error is reported 3 times in 2 hours, the compressor cannot turn
on. The unit needs to be restarted after temporary power disconnection. If all the
compressors of the unit send alarms, the unit will automatically turn off to prevent
damages.
E856DHD:
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...