61
1.2.2 Connecting to the power supply for preheating
Make sure that the unit is connected to the power supply at least 8 hours before operation,
so as to protect compressor (crankcase heating belt) and to confirm power phase
sequence, magnitude of voltage and three-phase equilibrium.
1.2.2.1 IDU drainage test
Remove the baffle plate
from IDU water inlet
Inject water through the
water inlet
When water level switch
changes from closed to
open status, or when FB2
port on IDU control board
is constantly open
(remove connecting wire),
IDU water pump operates