171
fault
fault
28H
3
Communication faults
1. Report sending fault for
upper computer
49H
12
Wrong address signal
1. Hall sensor fault
4AH
13
No address signal
1. Hall sensor fault
52H
17
EEPROM fault
1. Module EEPROM fault
Protection
34H
7
Under-voltage
protection
1. Voltage input is too low
(< 154 V)
35H
8
Over voltage
protection
1. Voltage input is too high
(> 283 V)
39H
9
Overcurrent protection
1. Fan is overloaded;
2. Fan starts spinning fast;
3AH
10
Short circuit protection
1. Fan power cord is
shorted;
2. Fan is shorted;
45H
11
Overheat protection
1. Module dissipates heat
poorly;
2. Ambient temperature is
too high;
2AH
5
Locked rotor
protection for motor
1. Fan fault
29H
4
Motor stall protection
1. Fan power cord UVW is
reversely connected
2. Hall sensor fault
2BH
6
Motor over-speed
protection
1. Hall sensor fault
4BH
14
Wrong operating
direction protection
1. Fan power cord UVW is
reversely connected
2. Hall sensor cable is
reversely connected
Summary of Contents for P70131000000
Page 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Page 38: ...38 Heating mode ...
Page 46: ...46 4 1 Remote controller instructions Functions ...
Page 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Page 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Page 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Page 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Page 131: ...131 2 Low voltage is too low ...
Page 149: ...149 ...
Page 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Page 151: ...151 2 23 Trip ...
Page 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...