Section 2
2-2 ThermoFlex
Thermo Scientific
• Cooling capacity based on P 2 pumps with no backpressure. Heat input from the pump will
result in a reduction in cooling capacity. The cooling capacity reduction will vary based on the
pump chosen as well as pump backpressure and flow.
• Specifications obtained at sea level using water as the recirculating fluid, at a 20°C
process setpoint, 25°C ambient condition, at nominal operating voltage. Other fluids, fluid
temperatures, ambient temperatures, altitude or operating voltages will affect performance.
See Section 3.
• Additional dimensions are at the end of this section, add 1/8" (3 cm) to height for SEMI.
• Add 30 pounds (14 kilograms) for global voltage chillers.
• Thermo Fisher Scientific reserves the right to change specifications without notice.
Specifications
* Pressure values for turbine and centrifugal pumps are differential pressures between the inlet
and the outlet of the chiller.
ThermoFlex3500
ThermoFlex5000
Process FluidTemperature
+5°C to +40°C
+5°C to +40°C
and Setpoint Range
+41°F to +104°F
+41°F to +104°F
Ambient Temperature Range
+10°C to +40°C
+10°C to +40°C
+50°F to +104°F
+50°F to +104°F
Temperature Stability
± 0.1°C
± 0.1°C
Cooling Capacity at 20°C
60
Hz
3500
W (11953
BTU)
5000
W (17076
BTU)
50
Hz
3050
W (10416
BTU)
4400
W (15027
BTU)
Refrigerant
R407C
R407C
Reservoir Volume
Gallons
1.9
1.9
Liters
7.2
7.2
Footprint or Dimensions (H
x
W
x
D)
Inches
38.9 x 19.3 x 30.9
38.9 x 19.3 x 30.9
Centimeters
98.7 x 48.8 x 78.4
98.7 x 48.8 x 78.4
Weight P
1/ P
2/P
3/P
4 (empty)
lb
264/264/270/303
NA/264/270/303
kg
120/120/123/138
NA/120/123/138
Pumping Capacity
P
1/MD
1 - Positive Displacement 60
Hz
*
2.1 gpm @ 60 psig (7.9 lpm @ 4.1 bar)
Not Available
50
Hz
*
1.7 gpm @ 60 psig (6.4 lpm @ 4.1 bar)
Not Available
P
2/MD
2 - Positive Displacement 60
Hz
*
4.0 gpm @ 60 psig (15.1 lpm @ 4.1 bar)
4.0 gpm @ 60 psig (15.1 lpm @ 4.1 bar)
50
Hz
*
3.3 gpm @ 60 psig (12.5 lpm @ 4.1 bar)
3.3 gpm @ 60 psig (12.5 lpm @ 4.1 bar)
T
1 - Turbine 60
Hz*
3.5 gpm @ 60 psid (13.3 lpm @ 4.1 bar)
3.5 gpm @ 60 psid (13.3 lpm @ 4.1 bar)
50
Hz*
2.5 gpm @ 60 psid (9.5 lpm @ 4.1 bar)
2.5 gpm @ 60 psid (9.5 lpm @ 4.1 bar)
P
3 - Centrifugal Pump
60
Hz*
10 gpm @ 32 psid (37.9 lpm @ 2.2 bar)
10 gpm @ 32 psid (37.9 lpm @ 2.2 bar)
50
Hz*
10 gpm @ 20 psid (37.9 lpm @ 1.4 bar)
10 gpm @ 20 psid (37.9 lpm @ 1.4 bar)
P
4 - Centrifugal Pump 60
Hz*
15 gpm @ 57 psid (56.8 lpm @ 3.9 bar)
15 gpm @ 57 psid (56.8 lpm @ 3.9 bar)
50
Hz*
15 gpm @ 34 psid (56.8 lpm @ 2.3 bar)
15 gpm @ 34 psid (56.8 lpm @ 2.3 bar)
Summary of Contents for ThermoFlex10000
Page 2: ......
Page 36: ...ThermoFlex900 5000 Thermo Scientific...
Page 42: ...DI SDS 4 0 gpm 15 1 lpm ThermoFlex900 5000 Thermo Scientific...
Page 79: ...517 2014 16 2014 ThemoFlex24000...
Page 100: ...Section 2 2 20 ThermoFlex Thermo Scientific...
Page 136: ...Section 4 4 14 ThermoFlex Thermo Scientific...
Page 168: ...Section 7 7 14 ThermoFlex Thermo Scientific...
Page 191: ...C 10 ThermoFlex Appendix C Thermo Scientific...
Page 208: ......
Page 209: ......