Section 4
4-12 ThermoFlex
Thermo Scientific
yES
no
drAin
StorE
drAin
enter
enter
SEr
xx
xx
LoFLO
LoFLO
enter
enter
Figure 4-7
Setup Loop (Optional Features)
•
LoFLO
is used to set the low flow alarm limit.
T 0 Pump
Range:
0.0 to 10.5 GPM
Default:
0.0 GPM
T 1 Pump
Range:
0.0 to 10.5 GPM
Default:
0.0 GPM
T 5 Pump
Range:
0.0 to 15.0 GPM
Default:
0.0 GPM
P 1 Pump
Range:
0.0 to 10.5 GPM
Default:
0.0 GPM
P 2 Pump
Range:
0.0 to 10.5 GPM
Default:
0.0 GPM
P 3 Pump
Range:
0.0 to 30.0 GPM
Default:
0.0 GPM
P 4 Pump
Range:
0.0 to 30.0 GPM
Default:
0.0 GPM
P 5 Pump
Range:
0.0 to 30.0 GPM
Default:
0.0 GPM
Going below the low limit flashes
LoFLO
and, if
enabled, sounds the alarm. The chiller's reaction depends
on the alarm (
ALr
) setting.
This feature is not enabled until the value is changed to
something other than 0.0. If the feature is not enabled
and the flow rate drops below the flow rate listed below
the chiller will continue to run and the controller will flash
between
FLo
and
LoFLo
.
P
1, T
0, T
1 and T
5 Pump
0.3 GPM
P
2 Pump
1.0 GPM
P 3, P
4 and P
5 Pump
4.0 GPM
•
SEr
is used to configure the serial communications
mode of operation. See Appendix D.
Note
Keypad operation is still available with serial com-
munications enabled.
•
drAin
is used to open and close the chiller's anti
drainback valve for draining, see Section 5.
Range:
yes or no
Default:
no
Note
The chiller must be off to drain the valve. The valve
automatically closes when you exit the
drAin
display.
When the display indicates
StorE
press
to save
all
changes or press
to not save
all
changes. The display will return either the process fluid
temperature or, if the chiller was off when you entered
the loop, a blank screen.
Continued from previous page
Save all changes
Do not save all changes
Summary of Contents for ThermoFlex10000
Page 2: ......
Page 36: ...ThermoFlex900 5000 Thermo Scientific...
Page 42: ...DI SDS 4 0 gpm 15 1 lpm ThermoFlex900 5000 Thermo Scientific...
Page 79: ...517 2014 16 2014 ThemoFlex24000...
Page 100: ...Section 2 2 20 ThermoFlex Thermo Scientific...
Page 136: ...Section 4 4 14 ThermoFlex Thermo Scientific...
Page 168: ...Section 7 7 14 ThermoFlex Thermo Scientific...
Page 191: ...C 10 ThermoFlex Appendix C Thermo Scientific...
Page 208: ......
Page 209: ......