Specifications
153
Standby Power Cord Requirements
Supply Circuit Breaker: 12 HP Motor 230/3/60
70 amps
12 HP Motor 460/3/60
40 amps
19 HP Motor 460/3/60
60 amps
Extension Cord Size:
12 HP Motor 230/3/60
(All 4 conductor, 2000 Vac, Type W Power Cable)
8 AWG Power Cable, 25 to 50-foot length
12 HP Motor 230/3/60
6 AWG Power Cable, 75-foot length
12 HP Motor 460/3/60
10 AWG Power Cable, up to 75-foot length
19 HP Motor 460/3/60
8 AWG, Power Cable, up to 75-foot length