Page 17
Apr-21-2016 DI-602A 320 DS (NZ313)_UL_April 2016
Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
SP1
SP3
SP4
SP5
SP6
SP2
F1
P
F2
CODE 1 - Display Configuration
Setpoint
Annunciators
Mode
First Digit
Update
Display Mode
Second Digit
Manual
Loader Mode
Second Digit
Display Functions
Mode
Second & Third Digits
Data
Source
Sub-menu
[X5X]
Display
Format
Sub-menu
[X6X]
Last Digit
Text Character
Sub-menu
[X7X]
1st
Digit
3rd
Digit
2nd
Digit
Setpoint Annunciators Mode
The setpoint annunciators mode is configured by changing the
first digit in Code 1. The setpoint annunciators can be configured
to operate as follows:
• On when the setpoint activates.
• All annunciators are permanently on and each one only goes
off when its setpoint activates.
• All annunciators are always off (See Note 1 on Code 1 diagram
on Page 18).
• Setpoint
1
annunciator comes
on
indicating a
rising
signal
.
Setpoint
2
annunciator comes
on
indicating a
falling
signal
.
The example procedure on Page 22 shows how to select the
setpoint annunciators to come ON when the setpoints are OFF
(not active).
Update Display at Selected Sample Rate
The meter’s default display update rate is 0.5 seconds and is
set in the second digit of Code 1 as [X0X].
The display can be configured to update at the input signal sam-
ple rate selected in Code 2.
The example procedure on Page 22 shows how to configure
the display to update at typically 10 samples per second by
setting Code 1 to [X2X].
For these settings to take effect, the analog sample rate must be
set at [2XX] in Code 2. See
Code 2 – Channel 1 Measurement
Task and Sampling Rate
on Page 23 for an example.
Manual Loader Mode
The meter can be configured to function exclusively as a man-
ual loader by setting Code 1 to [X1X].
See
Analog Output Module Supplement
for full details on
manual loader mode functions.
Display Functions Mode
The display functions mode in Code 1 allows you to configure:
• The data source for the primary display.
• The format of the display with last digit rounding, type of display
units, and decimal point placement.
• A text character for the last digit.
The display functions mode is configured by changing the sec-
ond and third digits in Code 1:
CODE 1 – Display Configuration Modes
All meter display modes, except the display brightness mode,
are configured in Code 1 (See diagram below). See Code 1
diagram on Page 18 for a breakdown of first, second, and third
digit settings.
• Selecting [X5X] enters the
Data Source
sub-menu.
• Selecting [X6X] enters the
Display Format
sub-menu.
• Selecting [X7X] enters the
Last Digit Text Character
sub-
menu.
Data Source – Second Digit [X5X]
The data source for the primary display is configured by selecting
5
in the second digit and the
0
in the third digit.
Note:
[XX1] Second Display is the bargraph display on models
DI-50EB51, DI-50TB51, FI-B101D50E, and FI-B101D50T.
The [XX1] Second Display and [XX2] Third Display only
apply to DI-503 meters with three displays.
The second digit in Code 1 can also be used to configure the
data source for the remaining functions in the third digit:
• [X53] = Peak and Valley.
• [X54] = Analog Output 1.
• [X55] = Analog Output 2.
• [X56] = Totalizer 1.
• [X57] = Totalizer 2.
Selecting
5
in the second digit enters a sub-menu and allows
you to select the data from one of a number of meter registers
as the data source for the displays or functions selected in the
third digit.
The example procedure on Page 19 shows how to select the
data source for the
primary
display. The three digits are set to
[
X50
].
Display Format – Second Digit [X6X]
Selecting
6
in the second digit enters the Display Format sub-
menu where the following display format settings can all be
configured:
• Last digit rounding.
• Display units (Decimal, octal, or optional 12 or 24-hour clock).
• Decimal point placement.
The example procedure on Page 20 shows how to configure
the three display format modes for the third digit selection.
Text Character – Second Digit [X7X]
Selecting
7
in the second digit allows you to select one of 54
characters and apply it to the last digit when the meter is in the
operational display.
For example, if the meter was measuring a temperature, the
display could be configured to display the reading with a C or
an F in the last digit for °C or °F.
The example procedure on Page 21 shows how to configure
the last digit text character as “C” for centigrade (°C) for the
third digit selection.
Note:
After setting any or all the above three modes [X5X], [X6X],
[X7X], the Code 1 display must set back to [X0X] to leave
Code 1 and carry on programming.
Initial Setup Procedures
[CodE_1] - Display Configuration