4 Guide to the Routine Maintenance Using the System
Monitor Interface
NetBackup 5020
Routine Maintenance
4-16
Symantec Corporation Issue 01 (2010-12-10)
Table 4-6
Description of parameters related to the power supply status
Parameter
Description
Status
The running state of the power supply.
Presence detected
indicates that the power supply works
normally.
Failure detected
indicates that the power supply is absent or
faulty.
Wattage
The power value of the power supply. Unit:
Watts
.
The value of
Wattage
ranges between
LowWaterMark
and
HighWaterMark
, that is, between
1 Watts
and
700 Watts
.
LowWaterMark
Lowest value of the power supply. The value is
1 Watts
.
HighWaterMark
Highest value of the power supply. The value is
700 Watts
.
ErrorStatus
Power supply status.
If the value of ErrorStatus is
0
, it indicates that a power supply is
working normally.
If the value of ErrorStatus is
1
, it indicates that a power supply is
working abnormally.
----End
Exception Handling
If the power supply is in the
Failure detected
state, see “Power Module Alarm” in the
NetBackup 5020 Hardware Troubleshooting
.
4.7 Checking Temperature
This section describes how to check the temperature on the system monitoring interface.
Impact on the System
None.
Reference Standard
The normal temperature of the
Intake Vent Temp
,
Outtake Vent Temp
, and
Backplane
Temp
ranges between
-10°C
to
+75°C
.
Procedure
Step 1
Log in to the system monitoring interface.
For the detailed procedure, see