P_108
96
hour
Valve exercise (h) 0=Not used
min
0
max 168
Indicates how often the valves should
be exercised (how many hours shall pass
between two exercise runs).
P_109
20 min
Motion timer delay (min)
min
0
max 60
Indicates the number of minutes after which
the controller should switch from AUTO to
ECON after the last occupant has left the
room.
P_110
60
min
Warning delay from start-up (min)
min
0
max 720
Indicates after how many minutes after
start-up the controller is allowed to initiate
an alarm.
The alarm is deactivated when the time delay
= 0.
P_111
120 min
Warning delay, PI-overload (min)
min
0
max 720
Indicates after how many minutes the system
should initiate an alarm for a +100% or
-100% output signal.
The alarm is deactivated when the time delay
= 0.
P_112
120 min
Warning delay, Set point (min)
min
0
max 720
Indicates after how many minutes the system
should initiate an alarm, if the set point for
temperature, flow or pressure has not been
reached.
The alarm is deactivated when the time delay
= 0.
P_113
30
min
Warning delay, pressure sensor (min)
min
0
max 720
Indicates after how many minutes the system
should initiate an alarm if no pressure or flow
sensor is detected.
The alarm is deactivated when the time delay
= 0.
P_114
0
Room Number (optional)
min
0
max 32000
Indicates the room number.
P_118
0
h
Zero calibration (h) 0=not used
min
0
max 720
O-point calibration of
MB pressure sensor. Enter hours between
calibration.
P_119
3
min
Zero calibration wait (min)
min
1
max 6
Delay before calibration starts. (to allow the
dampers time to close)
P_120
set
2
ID
BMS Modbus Address
min
1
max 247
Modbus address for the pipe work contractor
in BMS mode (Modbus 1)
P_121
1
Condense sensor measure method
min
0
max 1
Choice of method for condensation
measurement 0=Fixed limits, 1=Adjustable
limits
P_122
500 kOhm
Condense sensor wet limit
min
0
max 10000
Condensation sensor wet limit. Active when
P_121=1
P_123
900 kOhm
Condense sensor dry limit
min
100
max 10000
Condensation sensor dry limit. Active when
P_121=1
CONDUCTOR
W4
56
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...