Changes and settings in the Service menu
To set the air damper for supply air and to change the
K-factor
Service Menu
<Exit
Select>
Regulator adjust
..
Settings
......................
..
<Exit
Next>
K-factor SA1
Norm SA1 l/s
Boost SA1 l/s
5.0
20
30
OK select
Figure 6. Image for selecting Regulator adjustment settnings and view for setting the K-factor
and the damper for supply air in air duct 1.
1. Go to the Service menu.
2. Highlight the Regulator adjustment settings.
3. Press OK or on the
►
Right key.
4. Highlight the line of the value you want to change by pressing the
▲
UP key or the
▼
DOWN key.
5. Press OK to highlight the value.
6. To change the value:
• K-factor.
• Norm = the value applicable to normal airflow.
• Boost = the value applicable to high airflow.
7. Press OK to confirm the change.
8. Press the
►
Right key for advancing further and changing the values of
K-factor and supply air in air duct 2. (W4.2 only)
9. Press the
◄
Left key twice to return to the Service menu.
CONDUCTOR
W4
42
Swegon reserves the right to make design changes.. 20210201