Conductor W4 BMS, applies to software from 1.48
Default values from parameter file
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
Default
4x0037
Not used
4x0038
Economy flow, % of
normal flow
0/100
(%)
0
4x0039
NHoliday flow, % of
normal flow
0/100
(%)
10
4x0040
Not used
4x0041
Not used
4x0042
Boost flow SA1
0/5000
l/s
30
4x0043
Boost flow SA2
0/5000
l/s
30
4x0044
Not used
4x0045
Not used
4x0046
Not used
4x0047
Not used
4x0048
P term Heat
1/10000
Scale 1:100
5000
4x0049
I term Heat
1/10000
Scale 1:100
5
4x0050
P term Cool
1/10000
Scale 1:100
5000
4x0051
I term Cool
1/10000
Scale 1:100
5
4x0052
P term Change over
1/10000
Scale 1:100
5000
4x0053
I term Change over
1/10000
Scale 1:100
5
4x0054
SA 0% value
0/5000
0
4x0055
SA 100% value
5000/10000
10000
4x0056
EA 0% value
0/5000
0
4x0057
EA 100% value
5000/10000
10000
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
0-50
(degC) Only used in Manual state
4x0064
Relative flow in manual
mode
1/3
1=Eco flow, 2=Normal flow, 3=Boost
flow. Only used in Manual state
4x0065
Not used
4x0066
CO2 min level
350/1000
(ppm)
500
4x0067
CO2 max level
350/2000
(ppm)
1000
4x0068
CO2/Volt
10/500
(ppm/volt)
200
4x0069
Copy of Coil Status 1-16
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
CONDUCTOR
W4
70
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...