1. Connect the valve actuator for cooling water to wiring terminals 27 and
29 respectively.
2. Connect the presence sensor to wiring terminals 12 and 26 respectively.
3. Connect the window contact (normally closed or normally open) to
wiring terminals 10 and 25 respectively.
4. Connect the pressure sensor to the Modular contact. Set the address
on sensor.
SA1 = 3
SA2 = 6
EA = 4
5. Connect the carbon dioxide sensor as follows:
• 0-10 V signal: Wiring terminal no. 16
• G: Wiring terminal no. 21.
• G0: Wiring terminal no. 22.
6. Connect the wires of the condensation sensor to wiring terminals
17 and 18 respectively. NOTE! May vary depending on the type of
condensation sensor.
7. Connect the wires of the temperature sensor to wiring terminals 19 and
20 respectively
8. Connect the secondary side cables of the transformer to wiring
terminals 23 (G) and 24 (GO) respectively.
9. Connect the valve actuator for heating water as follows:
• Relay contact located under the casing of the controller.
• To wiring terminal no. 23.
• To wiring terminal no. 24.
10. Connect the damper motor for extract air as follows:
• G0: Wiring terminal no. 36.
• 0-10 V signal: Wiring terminal no. 37.
• 24 V: Wiring terminal no. 38.
11. Connect the damper motor 1 for supply air as follows:
• G0: Wiring terminal no. 33.
• 0-10 V signal: Wiring terminal no. 34.
• 24 V: Wiring terminal no. 35.
12. Connect the damper motor 2 for supply air as follows:
• G0: Wiring terminal no. 30.
• 0-10 V signal: Wiring terminal no. 31.
• 24 V: Wiring terminal no. 32.
CONDUCTOR
W4
30
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...