Display image
Description
P_1937
Offset flow EA (l/s)
0 l/s
Min -100
Max 100
Indicates the offset flow in the
extract air duct.
P_1938
Economy flow, % from Normal flow
50 %
Min 3
Max 100
Indicates how large portion of
the normal flow that should be
economy flow.
P_1939
Min SA1 Pressure (Pa)
0 Pa
Min 0
Max 100
Indicates what the lowest
pressure could be in supply air
duct 1, in order to ensure the
function.
P_1940
SA1 mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1941
SA1 mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1942
SA2 mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1943
SA2 mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1944
EA mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1945
EA mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1946
SA1 damper after sensor error
50 %
Min 0
Max 100
Displays start position on supply
air 1 after an error on the
sensor.
P_1947
SA2 damper after sensor error
10 %
Min 0
Max 100
Indicates the start position on
supply air 2 after an error on
the sensor.
P_1948
EA damper after sensor error
50 %
Min 0
Max 100
Indicates start position on the
extract air after an error on the
sensor.
CONDUCTOR
W4
60
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...