P_1972
Not used flow from Normal flow
10
Min 0
Max 100
Indicates what percentage
of the normal airflow will be
discharged into the room when
it is not occupied for a longer
period.
P_1973
Two step heating 1=OFF, 2=ON
1
Min 0
Max 1
Activates provision for extra
heating output.
P_1974
Two step delay (min)
5 min
Min 0
Max 30
Indicates the time delay for
switching on extra heating.
P_1975
Relay use 0=OFF, 1=ON
1
Min 0
Max 1
Activates/deactivates the
controller’s relay function.
P_1976
Commissioning Air
0
Min 0
Max 4
Choice of commissioning
mode, Air
0=Off, 1=Airflow, No
occupancy, 2=Airflow, Min.
occupancy, 3=Airflow, Max.
occupancy, 4=Airflow, Holiday
P_1977
Commissioning Water
0
Min 0
Max 2
Choice of commissioning
mode, Water
0=Off, 1=Cooling valve fully
open, 2=Heating valve fully
open
P_1978
Cold draught protection, 0=OFF
0%
Min 0
Max 100
Indicates the level of the output
signal for heated water valve
actuators.
P_1979
Cdp cool output level
30%
Min 0
Max 100
Indicates maximum cooling
load before the heat is switched
off.
P_1980
4-pipe POS max
100%
Min 0
Max 100
Output signal’s voltage level at
a heating signal of 100%
P_1981
4pipe POS min
65%
Min 0
Max 100
Output signal’s voltage level at
lowest heating signal
P_1982
4pipe NEG max
55%
Min 0
Max 100
Output signal’s voltage level at
a cooling signal of 100%
P_1983
4pipe NEG min
20%
Min 0
Max 100
Output signal’s voltage level at
lowest cooling signal
63
20210201 Swegon reserves the right to make design changes.
CONDUCTOR
W4
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...