Actuator Heat 1=NO, 2=NC (On Relay, X-15)
2
Min 1
Max 2
Indicates the type of valve
actuators that are used to heat
water
1=24V-NC
2=24V-NO
P_1962
Boost at arrival 0=No 1=Active
1
Min 0
Max 1
Indicates whether time-adjusted
flow boost is accessible.
(0=No, 1=Yes)
P_1963
Boost at arrival time (min)
5
Min 1
Max 300
Indicates how long the
timeadjusted flow boost should
be on ON when occupancy is
activated
P_1964
Conference, Office or VAV
2
Min 1
Max 2
Select function. Conference
room (two supply air dampers)
hotel/office or VAV
1=W4.2 (Conference room)
2=W4.1 (Hotel) 3=VAV
P_1965
ActuatorHeat 1=NC, 2=0-10V, 3=NO
(30-31-32, X-12)
1
Min 1
Max 3
W4.1 function for actuator,
heat
1= Normally closed
2= 0-10V
3= Normally open
P_1966
TC_Normal
23
Min 15
Max 35
Switch in cooling for normal
operation.
P_1967
TH_Normal
21
Min 15
Max 35
Switch in heating for normal
operation.
P_1968
TC_Economy
25
Min 10
Max 35
Switch in cooling for economic
operation.
P_1969
TH_Economy
19
Min 10
Max 35
Switch in heating for economic
operation.
P_1970
TC_Holiday
27
Min 10
Max 30
Switch in cooling for holiday
operation.
P_1971
TH_Holiday
17
Min 10
Max 35
Switch in heating for holiday
operation.
CONDUCTOR
W4
62
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...