Water – Air with temperature control
Flow %
100%
50%
20%
No
occupancy
Occupancy
CO
2
Air 1
Temperature
Water
Air 2
Temperature/CO
2
26
°
C
1000 PPM
24
°
C
800 PPM
22
°
C
600 PPM
Time period
Figure 8. Typical diagram dealing with the water-to-air sequence with temperature control.
Note! Air 2 is valid only for W4.2
The sequence involves the following: If occupancy is registered in the room
and if the temperature is at a certain level, the system starts a cooling
process that cools down the room by circulating chilled water in the water
pipes.
If the temperature rises more and the chilled water is not sufficient for
maintaining the required temperature, the cooling process is supplemented
by increasing the airflow.
If the level of carbon dioxide in the room exceeds a certain level, the airflow
is increased in order to reduce the level and keep it constant.
Operating Mode
Depending on the status of connected sensors, the controller adjusts the
outputs from any of several possible operating conditions.
The various operating conditions described here are based on occupancy
in the room and the status of the window contact, condensation sensor,
carbon dioxide sensor and the current pressure.
Occupancy Window
Condensation
Carbon
dioxide
Airflow Cooling
No
No
No
No
Low
ECON
Yes
No
No
No
Normal
Normal
Yes
Yes
No
No
Low
Closed
Yes
No
Yes
No
High
Closed
Yes
No
No
Yes
High
Normal
Yes
No
No
No
Normal
Normal
CONDUCTOR
W4
14
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...