Display image
Description
P_1913
Room unit´s max set point
28
°
C
Min 0
Max 50
Indicates which highest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
P_1914
Heat ON limit
10
%
Min 5
Max 50
Indicates at which output signal
for heating the relay contact
closes and the heat source is
opened.
P_1915
Heat OFF limit
5
%
Min 5
Max 10
Indicates at which output signal
for heating the relay contact
opens and the heat source is
disconnected.
P_1916
Delay between heat ON/OFF
5 min
Min 1
Max 25
Indicates what the delay
should be between when the
heat source is connected or
disconnected. The purpose
of this is to prevent the relay
contact from closing and
opening too often.
P_1917
P term Heating Scale 1:100
5000
Min 1
Max 10000
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1918
I term Heating Scale 1:100
5
Min 1
Max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1919
P term Cooling Scale 1:100
5000
Min 1
Max 10000
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1920
I term Cooling Scale 1:100
5
Min 1
Max 10000
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1921
P term Change over
5000
Min 1
Max 10000
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
P_1922
I term Change over
5
Min 1
Max 10000
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
P_1923
C02 Control, 0=No, 1=Active
0
Min 0
Max 1
Indicates whether the installed
carbon dioxide sensor is
connected or not.
0 = Not connected
1 = Connected
P_1924
C02 min level ppm
500 ppm
Min 350
Max 1000
Indicates at which lowest
carbon dioxide content in
the room the airflow should
increase.
CONDUCTOR
W4
58
Swegon reserves the right to make design changes.. 20210201
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...