Set point step for selection of temperature display in
whole and half degrees
Base screen mode
<Exit
Select>
Set point step
Commissioning
......................
Set point step
<Exit
Figure 19. Image for selecting the base screen mode and image for the Base screen mode
function.
1. Go to the Service menu.
2. Highlight Settings.
3. Press OK or on the
►
Right key.
4. Highlight the Set point step.
5. Press OK or the
►
Right key.
6. Change by pressing the
▲
UP key or
▼
DOWN key to choose between
temperature display in whole or half degrees.
7. Press OK to confirm the change and return to the Settings menu.
8. Return to the Service menu by pressing the
◄
Left key.
[0,5°C]
Commissioning
Commissioning
<Exit
Water
AIR
Commissioning
<Exit
Cool valve
Heating valve
Backlight
<Exit
Basescreen mode
Commissioning
Select>
....
....
....
....
....
..
Figure 20. Image for selecting commissioning and image for the Commissioning function.
1. Go to the Service menu.
2. Highlight Settings
3. Press OK or press on the
►
Right key..
4. Highlight Commissioning.
5. Press OK or on the
►
Right key.
6. Change by pressing the
▲
UP key or
▼
DOWN key to choose between
Water and Air
7. Press OK to confirm the change and return to the Settings menu
8. Return to the Service menu by pressing the
◄
Left key.
51
20210201 Swegon reserves the right to make design changes.
CONDUCTOR
W4
Summary of Contents for 20210201
Page 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Page 2: ......
Page 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Page 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Page 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Page 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Page 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...