A P P E N D I X
B
Remote and Local Power
Management
This appendix describes how to enable remote power management for the Sun
StorEdge 6920 system. It includes the following sections:
■
“Preparing the System for Remote Power” on page 80
■
“Performing a Partial System Shutdown” on page 91
■
“Performing a Full System Shutdown” on page 93
■
“Restoring Power to the System” on page 96
When the remote power-on and power-off feature is enabled, the configuration
management GUI allows you to perform a partial system shutdown from a remote
location. When the system is in the partial shutdown state, the Storage Service
Processor and the Storage Service Processor accessory tray remain powered on and
active, to facilitate a future remote power-on operation.
Caution –
Do not use the partial remote power-off sequence when moving the
system. You must completely power off the system, as described in “Performing a
Full System Shutdown” on page 93, before moving it.
Note –
If you are installing a Sun StorEdge 6920 system with an expansion cabinet,
perform the procedures in this appendix for both cabinets.
Summary of Contents for StorEdge 6920 System
Page 7: ...Contents vii E Information Collection Worksheet 109 Glossary 111 Index 119 ...
Page 8: ...viii Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 12: ...xii Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 18: ...xviii Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 54: ...36 Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 92: ...74 Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 96: ...78 Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 118: ...100 Sun StorEdge 6920 System Getting Started Guide May 2004 ...
Page 136: ...118 Sun StorEdge 6920 System Getting Started Guide May 2004 ...