1
C H A P T E R
1
Before Installation
This section provides information on what should be considered when choosing a
location for a Netra ft 1800 system.
Note –
This equipment is only intended for installation in a Restricted Access
Location as defined by UL1950, 3rd Edition, and EN60950: 1992 / A11: 1997.
Electrical Supply Considerations
Before you install the system, verify that the correct power supply is available. Refer
to “DC Source Site Requirements” on page 44 for further information.
Environmental Considerations
The system can be installed in an environment with the following specific parameter
ranges:
■
Ambient temperature
■
Operating: 0 to 40 degrees Celsius (short term operation up to a temperature of
50 degrees Celsius is possible; however, the operation of removable media
devices cannot be guaranteed.)
■
Storage: –40 to 70 degrees Celsius
Summary of Contents for Netra ft 1800