Operating instruction Z7510 Multizone temperatur controller
I
Temperatur controller
68
STRACK NORMA GmbH & Co. KG · Königsberger Str. 11 · D-58511 Lüdenscheid · Tel +49 2351 8701-0 · www.strack.de
08.2018
Operations manual NR4000-v.2
68
- PROFIBUS DP
off
Profibus: read-only / opera-
Remote :
tion on the device possible.
Profibus can read parameters
but not alter them.
on
Profibus: read / write
Operation on the device not
possible.
(
factory default
)
- PROFIBUS DP
1 .... 125 (
factory default : 1
)
Device adress :
- PROFIBUS DP
Baudrate is detected and displayed auto-
Baudrate
maticly. It can not be altered
Display :
Not detected
12 MBaud
6 MBaud
3 MBaud
1,5 MBaud
500 kBaud
187,5 kBaud
93,75 kBaud
45,45 kBaud
19,2 kBaud (not supported)
9,6 kBaud (not supported)