Operating instruction Z7510 Multizone temperatur controller
I
Temperatur controller
50
STRACK NORMA GmbH & Co. KG · Königsberger Str. 11 · D-58511 Lüdenscheid · Tel +49 2351 8701-0 · www.strack.de
08.2018
Operations manual NR4000-v.2
50
As current alarm :
Off =0,0; 0,1 … 99,9 A
(
factory default 1,0
)
- Self optimizing
:
off
Autotuning
(autotuning)
out of order
(
default
)
on
Autotuning
activated
for this zone
all
Autotuning
activated
for all zones
Automatically at every start-up
(mains power-on)
Autotuning determines automaticly the optimal PID-
parameters for every controlled system (=mould).
Only this guarantees a stable and precise tempera-
ture control,
that‘s why performing an autotuning
at least once for every mould is essential for a
stable operation.
General information about self-optimizing (autotuning) :
The optimizing algorithm calculates automatically the op-
timal PID-parameters (Xp, Tv and Tn) and the switching-
cycle time. With the setting „Automatic“, the autotuning is
performed at start-up after the softstart-phase below the
setpoint temperature. This one must be at least be 5% of