Device Adress:
Each device has it‘s own adress (1...125),
which will be programmed via parameter
„Device adress“. There are up to 32 device
adresses in one segment programmable.
With the help of a repeater, up to 127 devices
can be connected. The single controller zones
are called up within the protocol.
Special:
- Configuration channel für reading and
writing of all available parameters.
- Configurable process data moduls.
- Diagnostic warnings, to detect sensor-
and/or system errors.
- Easy connection to IPC‘s or PLC‘s.
Informations about the Profibus-
communication:
Select Parameter „Profibus DP : Baudrate“.
Bus-Status:
No Connection
Profibus not connected
or master not active.
Wait Param
Master detected . Device
expects parameter
Data Exchange
Data Exchange Modus
Error xxxx
Profibus-system error
Important:
Parameter „remote“ has to be set to „on“, otherwise,
it is not possible to write data into the device.