Operating instruction Z7510 Multizone temperatur controller
I
Temperatur controller
44
STRACK NORMA GmbH & Co. KG · Königsberger Str. 11 · D-58511 Lüdenscheid · Tel +49 2351 8701-0 · www.strack.de
08.2018
Operations manual NR4000-v.2
44
- Max. output ratio
0...100 %
limit „%“ :
Limitation of the output ratio is only necessary
when the heating element is largely overdi-
mensioned. Under normal circumstances, no
limitation is needed (
default setting = 100%
).
Attention !
The output ratio limitation does not work du-
ring autotuning.
- Rising ramp
off; 0,1 ...99,9 ° C/min. or °F/min.
(factory default :
off)
0,01...9,99 °C/min. or °F/min. if a
range with decimal point is selected
- Falling ramp
off; 0,1 ...99,9 ° C/min. or °F/min.
(factory default :
off)
A programmed ramp is always activated when
the setpoint is altered or when the mains
supply is switched on. The ramp can be acti-
vated for both setpoint 1 and setpoint 2.
- P-value
off; 0,1...100,0 %
Proportional
(
default : 3,0
)
band
If „off“, go to parameter „Cycle
time“.
- I-value
off; 1...1000 secs. (default : 150)
Reset time
(sec.)