DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
63
P 02.15 Event: Remote TCI too small
Default: W2 (Hidden)
Event Group: MF
Number: 14
Options:
NO
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)
This parameter selects the error condition generated when totalizer pulses for the Total Coal
Integrator (TCI) output are generated faster then the TCI output can operate. See parameter 02.12
for more information.
This parameter should be set to W2.
Action: Adjust the values of parameter P02.11 and P02.12.
P 02.16 Maintenance Speed
Default: 50%
Min: 0 %
Max: 100 %
This parameter determines the Motor Speed Control (MSC) demand signal used during maintenance
(local, calibrate, jog) operations. It is similar to 196NT Setup 01 (Speed Setpoint) except that the
MSC demand signal is set rather then the actual motor speed (open loop operation). The actual
motor RPM is determined by the characteristics of the motor and the MSC.
This parameter is normally set to 50% which will produce a motor speed of approximately 900 RPM
with a 4 pole, 60 Hz motor.
P 02.17 DO: FRI Frequency
VCU 20103 Default: DO 13 – High (Hidden)
Options:
n/a (not used)
DO 13 High/Low
This parameter specifies the digital output used for the Feed Rate Indicator (FRI). This parameter
output can only be set to DO 13 (terminal block X6-1 and X6-2) which is an isolated, unpowered,
transistor output.
P 02.18 Remote FRI Frequency
Default: 10.000 Hz/(t/h)
Min: 0.000 Hz/(t/h)
Max: 2,000,000.000 Hz/(t/h)
The value of this parameter is used to calculate remote Feedrate Indicator (FRI) output frequency. It
must be selected so that the FRI output at the minimum feedrate (see P03.06) is greater then 1.0 Hz
and the FRI output at the maximum feedrate (see P03.06) is less then 1000 Hz.
This parameter is normally set to 10.0 Hz / Ton/hr
Summary of Contents for DISOCONT Tersus DT-9
Page 2: ......
Page 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Page 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Page 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Page 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Page 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Page 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...