DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
133
Event Group: Electrical System
WE-01
Power Failure
( P 06.08 )
Normally disabled and hidden.
This event is generated when power is lost. If P06.08 Event: Power failure is set to A, the
feeder will be in OFF/Maint Mode when power is restored.
WE-02
Event: NAMUR Error V103-DI13
( P 15.05 )
This event should only be enabled when a NAMUR sensor is connected to DI 13.
The connection to the sensor on DI 13 (X5-5 and X5-6) has been lost.
Action:
•
Insure that a NAMUR device is connected to DI 13.
•
Check the DI 13 wiring.
WE-03
Event: NAMUR Error V103-DI14
( P 15.06 )
This event should only be enabled when a NAMUR sensor is connected to DI 14.
The connection to the sensor on DI 14 (X5-3 and X5-4)has been lost.
Action:
•
Insure that a NAMUR device is connected to DI 14.
•
Check the DI 14 wiring.
WE-08
Analog Input< Offset
( P 06.15 )
Normally disabled and hidden.
The signal available across an analog input is smaller than the set zero point elevation.
Action: Check analog input (Sig+ & Sig-) wiring.
Event Group: Interlock
IL-01
Run Disabled
( P 03.11 )
Normally set to W2.
When a touch screen HMI is used, parameter P03.10 Run Enable must be set to DI 8,
which is connected to the stop switch mounted under the HMI. This switch is used to stop
the feeder in the event that the HMI is disabled or disconnected. Parameter P03.11 is
normally set to W2 so that there is an indication on the display when the feeder is disabled.
Action:
•
Check the position of the Run Enable switch. Check the wiring to the Run
Enable switch.
Note: The Run Enable switch is not normally used with the Stock 196NT display and in this
case P03.10 Run Enable must be set to n/a to allow motor operation.
Summary of Contents for DISOCONT Tersus DT-9
Page 2: ......
Page 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Page 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Page 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Page 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Page 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Page 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...