DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
62
P 02.13 Totalizer Increment
Default: 100.00 lb
Min: 0.00 lb
Max: 100,000 lb
This parameter sets the weight associated with each Total Coal Integrator (TCI) pulse. It is the same
as 196NT Setup 07 (Remote Totalizer Data Logging Increment).
The TCI output frequency is based on parameter P02.11, parameter P02.12 and the actual feedrate.
If the values selected for these parameters require an output frequency greater then the maximum
frequency of the selected device, an error (MF 14 - P02.13) will be generated. See parameter P02.12
for more information.
This parameter is normally set to either 100 Lbs or 100 Kgs.
P 02.14 Remote Totalizer Pulse Width
Default: 0.100 s
Min: 0.000 s
Max: 10.000 s
This parameter sets the duration of each Total Coal Integrator (TCI) pulse. It is the same as 196NT
Setup 35 (Remote Totalizer Pulse Width).
The TCI output frequency is based on this parameter, parameter P02.11 and the actual feedrate. If
this combination of values requires an output frequency greater then the maximum frequency of the
selected device, an error (MF 14 - P02.13) will be generated.
The maximum pulse frequency can be calculated as:
Frequency = ( P03.05 Maximum Feedrate) / ((3600) x ( P02.11))
Where the maximum feedrate is in lbs/hr and P02.11 is in lbs.
When the TCI output is directed to an open collector or reed relay output the maximum possible pulse
frequency is 10 Hz (P02.12 set to 0.05 sec). When the TCI output is directed to a mechanical relay
output the maximum possible pulse frequency is 1.0 Hz (P02.12 set to 0.5 sec). When the pulse
length (P02.12) is increased, these values are reduced.
The maximum possible frequency (in Hz) is calculated as:
Max. possible freq. = 1 / (2 X P02.12 (in sec))
To insure that the TCI output works correctly the maximum pulse frequency must always be less then
the maximum possible frequency.
This parameter is normally set to 0.1 sec.
Summary of Contents for DISOCONT Tersus DT-9
Page 2: ......
Page 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Page 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Page 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Page 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Page 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Page 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...