9.2.17 Parameter Group 17 – Analog Calibration
The parameters in this group are used to trim the analog output values. They can be set manually
but they are normally set using he Analog Trim Function (see section 5.6)
P 17.01 Analog Input 1 Min
Default: 4.00 mA
Min: 1.00 mA
Max: 7.00 mA
See section 4.5, Analog Trim Function.
P 17.02 Analog Input 1 Max
Default: 20.00 mA
Min: 17.00 mA
Max: 23.00 mA
See section 4.5, Analog Trim Function.
P 17.03 Analog Input 2 Min
Default: 4.00 mA
Min: 1.00 mA
Max: 7.00 mA
See section 4.5, Analog Trim Function.
P 17.04 Analog Input 2 Max
Default: 20.00 mA
Min: 17.00 mA
Max: 23.00 mA
See section 4.5, Analog Trim Function.
P 17.05 Analog Input 3 Min
Default: 4.00 mA
Min: 1.00 mA
Max: 7.00 mA
See section 4.5, Analog Trim Function.
P 17.06 Analog Input 3 Max
Default: 20.00 mA
Min: 17.00 mA
Max: 23.00 mA
See section 4.5, Analog Trim Function.
P 17.07 Analog Input 4 Min
Default: 4.00 mA
Min: 1.00 mA
Max: 7.00 mA
See section 4.5, Analog Trim Function.
Summary of Contents for DISOCONT Tersus DT-9
Page 2: ......
Page 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Page 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Page 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Page 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Page 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Page 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...