10 | Connection
STOBER
124
02/2019 | ID 442728.05
10.5.7
X4B: Encoder B
The encoder of axis B is connected to X4B for double-axis controllers. Only X4A is available for
single-axis controllers. The connection description of X4B matches the X4A description.
10.5.8
X9: Ethernet service interface
X9 is used to connect the drive controller to a PC with installed DriveControlSuite
commissioning software.
Socket
Pin
Designation
Function
1|2|3|4|5|6|7|8
1
Ethernet communication
2
TxData−
3
R
4
—
—
5
—
—
6
RecvData−
Ethernet communication
7
—
—
8
—
—
Tab. 109: X9 connection description
Cable requirements
Feature
All sizes
Max. cable length
100 m, shielded
Tab. 110: Cable length [m]
Information
To ensure proper functionality, we recommend using cables from STOBER that are matched to
the complete system. In case of use of unsuitable connection cables, we reserve the right to
reject claims under the warranty.
It is also possible to use cables with the following specification:
Feature
Design
Connector wiring
Patch or crossover
Quality
CAT 5e
Shielding
SF/FTP, S/FTP or SF/UTP
Tab. 111: Cable requirements
Device addressing
Information for device addressing can be found in the chapter
.