STOBER
10 | Connection
02/2019 | ID 442728.05
117
10.5.2
X2A: Brake A
The brake of axis A is connected to X2A. All device types of the SI6 drive controller can control
a 24 V
DC
brake as standard.
Information
Note that brakes from other manufacturers may be connected only after consultation with
STOBER.
Controllable brakes
Note the technical data of the brakes controllable at X2A; see the chapter
Sizes 0 to 2 (single-axis controllers)
Term.
Pin
Designation
Function
5 | 6
5
1BD1
Brake actuation
6
1BD2
Reference potential
Tab. 96: X2A connection description, brake A, sizes 0 to 2 (single-axis controllers)
For connecting wiring, observe the terminal specifications in the chapter
.
Sizes 2 (double-axis controllers) and 3
Term.
Pin
Designation
Function
5 | 6
5
1BD1
Brake actuation
6
1BD2
Reference potential
Tab. 97: X2A connection description, brake A, sizes 2 (double-axis controllers) and 3
For connecting wiring, observe the terminal specifications in the chapter
.
Cable requirements
Motor connection
Size 0 to 2
Size 3
Without output choke
50 m, shielded
100 m, shielded
With output choke
100 m, shielded
—
Tab. 98: Maximum cable length of the power cable [m]